Building Code Clause F6 and F6/AS

The Department recently discussed the application of Building Code Clause F6 Visibility in Escape Routes with engineers and representatives of building consent authorities. Discussions particularly focused on the exemption allowed under performance criterion F6.3.1 of the Building Code and Acceptable Solution F6/AS1 Paragraph 1.2(c).

The Department wishes to clarify the situation as follows.

From any start point on an escape route to the nearest exit, where the length of travel is less than 20 m, the exemption from the provision of emergency lighting may apply.

Where, from any start point to the nearest exit, the travel distance is greater than 20 m, emergency lighting is required for the remainder of the escape route.

The nearest exit must be identified by signage complying with Building Code Clause F8. Where the exit is not visible from the start point on the escape route, directional signage complying with Clause F8 is also required.

Clause F6 requires consideration of visibility of specified features in escape routes only in the event of failure of the main lighting.